KNX
Connect to a KNX network via a KNX IP Interface/Router.
Agent configuration
The following describes the supported agent configuration attributes:
| Attribute | Description | Value type | Required |
|---|---|---|---|
host | IP Interface/Router hostname or IP address | Hostname or IP address | Y |
port | IP Interface/Router port | Port number | N |
NATMode | Enable NAT mode | Boolean | N (Default = false) |
routingMode | Enable Routing mode | Boolean | N (Default = false) |
messageSourceAddress | Source group address | Text (KNX Group Address e.g. 1.1.1) | N (Default = 0.0.0) |
Agent link
For attributes linked to this agent, the following describes the supported agent link fields which are in addition to the standard Agent Link fields:
| Field | Description | Value type | Required |
|---|---|---|---|
type | Agent type | Text (Must be KNXAgentLink) | Y |
dpt | The DPT (data point type) of the group address | Text (DPT e.g. 1.001) | Y |
actionGroupAddress | Group address for attribute write | Text (KNX Group Address e.g. 1.1.1) | N (Default = 0.0.0) |
statusGroupAddress | Group address for attribute read | Text (KNX Group Address e.g. 1.1.1) | N (Default = 0.0.0) |
Discovery and Import
To understand discovery and import refer to Agent and Asset Discovery/Import. This protocol supports the following:
- Protocol Asset Import (
*.knxproj)
Each group address in the project file will create a new asset with a single attribute also with the same name (no spaces in attribute name), the attribute type is determined by the following naming convention:
- Group Address ends with #A - Actuator (executable attribute)
- Group Address ends with #S - Sensor (read only)
- Group Address ends with #SA or #AS - Actuator and sensor
Only group addresses using this convention will be imported